Requirements: Hardware: CPU 1214C - 6ES7 214-1AG40-0XB0, CB1241 - 6ES7 241-1CH30-1XB0
Software: TIA Portal V15.1 or higher
Download TIA-project: link
In the example we read 3 registers from Device1 and write these values to Device2.
Reading data from device Device1 is performed in 2 requests: read 40001, read 40002,40003.
Writing to the Device2 device is performed in one request: writing to 40003, 40004, 40005.
The DB ModbusRtuMaster_DevicesDb.device1 contains the query configuration for Device1.
Request 1 (requests[0]): Read register 40001, place value in device1.buffer[0].
Request 2 (requests[1]): Read register 40002..40003, place values in device1.buffer[1]..device1.buffer[2]
The DB ModbusRtuMaster_DevicesDb.device2 contains the query configuration for Device2.
Request 1 (requests[0]): Write from device1.buffer[0]..device1.buffer[2] to registers 40003..40005.
The main logic is located in the function block ModbusRtu_Master
Initialization must occur once when the controller is started; for this, the FirstScan system flag is used.
If initialization is completed successfully, set token to poll the first device (i = 0)
REGION Serial port initialization
IF "FirstScan" THEN
#mbCommLoad.MODE := 4;
END_IF;
#mbCommLoad.RETRIES := #com.retries;
#mbCommLoad(REQ := "FirstScan",
"PORT" := #com."port",
BAUD := #com.baud,
PARITY := #com.parity,
MB_DB := #mbMaster.MB_DB,
RESP_TO := #com.timeout,
DONE => #com.done,
ERROR => #com.error,
STATUS => #com.status);
#initTrig(CLK := #com.done);
IF #initTrig.Q THEN
#i := 0;
END_IF;
END_REGION
To call instance of FB "LMBMD_ModbusDeviceRtu_Master" you need to send a single pulse to the start input.
#start := NOT #inst_LModbusDeviceRtu_Master.done;
Poll of device Device1 starts.
When all requests is completed the output done will be set to true once.
We start copying data from device1.buffer to DataDb.device (FC "ModbusRtu_Device1_MapData").
Set the next token (i := i + 1).
IF #inst_LModbusDeviceRtu_Master.done THEN
"ModbusRtu_Device1_MapData"(mdata := "ModbusRtuMaster_DevicesDb".device1,
data := "DataDb".device);
#i := #i + 1;
END_IF;
//"ModbusRtu_Device1_MapData"
#data.param1 := #mdata.buffer[0];
#data.param2 := #mdata.buffer[1];
#data.param3 := #mdata.buffer[1];
Before starting polling of Device2, the data to be written is moved from DataDb.device to device2.buffer (FC ModbusRtu_Device2_MapData).
//"ModbusRtu_Device2_MapData"
#mdata.buffer[0] := #data.param1;
#mdata.buffer[1] := #data.param2;
#mdata.buffer[2] := #data.param3;
Poll of device Device2 starts.
When all requests is completed the output done will be set to true once.
Set the next token (i := i + 1)
IF #inst_LModbusDeviceRtu_Master.done THEN
#i := #i + 1;
END_IF;
Tokens have run out, set the initial one and start the process again
ELSE
#i := 0;